Products

Position: Home -> Products > Pressure Reducing Valve

DP17E pilot operated pressure reducing valve
  • DP17E pilot operated pressure reducing valve

Product: DP17E pilot operated pressure reducing valve Pressure Rating: 1.6- 2.5Mpa Specification: DN15-50 Material: Steel WCB Standard flanges: DIN, ANSI, JIS

Details

 

 

 

DP17E Pressure Reducing Valve Structural characteristic and purpose

DP17E Pressure Reducing Valve is supplied as for the DP17 with a control spring but the maximum pressure is limited to 10 Bar g due to the addition of the solenoid valve. A solenoid operated valve is fitted in te pipe between the pilot valve and the main diaphragm camber and is thus in series with the normal pilot valve.

 

The purpose of the solenoid valve is to override the pilot valve thus causing the main valve to shut-off. It can be controlled by any device capable of interrupting the supply of current to the solenoid coil.

 

The dolenoid is arranged to open the valve when the coil is energised so that whatever switching device is used it must be arranged to break the current to close the main valve. In this way the unit will always fail-safe i.e. will close the main valve in the event of a failure in electrical supply.

 

Electrical supply

It is important that the solenoid is connected to the correct voltage. Therefore always check on the supply details which are stamped on the solenoid valve name-plate before attempting to connect up. Electrical connection is by cable plug to DIN 43650. All wiring, cnnectors, etc. in close proximity to the valve should be of heat resisting type and comply with local and national electrical codes.


This pilot operated reducing valve is the new type pilot extra-huge membrane pressure reducing valve developed by our company. It is greatly improved on basis of normal pressure reducing valve. The membrane use new material, enlarging the working area, so the slight change of upper pressure or lower pressure can be fed back to membrane of main valve, and adjust the opening of main valve to ensure the constant pressure of lower stream pressure.


Another outstanding advantage of the valve is: a valve body can be installed with many pilot valves, to realize the temperature control,

upper stream pressure control and long-distance switch control as well as pressure regulating.

 

DP17E Pressure Reducing Valve main technical parameters and indexes of performance
Nominal pressure
PN25
Maximun design pressure(PMA)
25bar g @ 120
Maximun design temperature(TMA)
232 @ 21bar g
Minimun design temperature(TMI)
-10
Maximun upstream pressure for saturated steam service(PMO)
10barg
Maximun operating temperature(TMO)
190 @ 21bar g
Minimun operating temperature(TMIO)
0
Maximun differential pressure( PMX )
10bar
Maximum cold hydraulic test pressure
38bar g

 

DP17E Pressure Reducing Valve material of main component
 

Name of component
Material of component
Valve body, valve cover
WCB
Valve seat
2Cr13
valve flap
2Cr13
Valve rod
2Cr13
Membrane
Brass
Adjusting spring
60Si2Mn

 

DP17E Pressure Reducing Valve connecting dimension
 

DN
L
H1
H
D
15
147
221
133
185
20
154
224
136
185
25
160
235
145
207
32
180
236
156
207
40
200
238
176
255
50
230
246
183
255
65
250
295
200
320
80
310
323
230
350
100
350
340
263
380
125
400
359
306
455
150
450
375
330
500

 

 

 

If you are interested in this product from us Goole Valve, you can feel free to contact us at +86-577-57781015 or goole4@goolevalve.com.

We will serve you with our GA Drawings or our E-Catalogs together with our Best Price. Thanks.

 

 

Hits:  UpdateTime:2024-09-12 16:09:11  【Printing】  【Close
  • Copyright (c) 2008-2015 Yongjia Goole Valve Co,.Ltd http://www.chinavalveworld.com E-mail: goole4@goolevalve.com
  • Address: He_yi Industrial Zone, Oubei Town, Wenzhou City, Zhejiang Province, P. R. China TEL: 86 - 577 - 57781015 FAX : 86 - 577 - 67985602
  • safety relief valve(our hot), pressure reducing valve and other steam trap,bellow sealed globe valve,ball valve, Y/T/U strainer
Online 
Ms Cathy Ms Cathy MSNMs Cathy